Type the code from the remote or the indoor unit. The meaning appears on the first character, with every unit type that uses it.
GENERAL's manuals for the exact O General models sit behind a download agreement, so these tables come from GENERAL's published service and installation manuals that share the same code system[1]. We confirm the code on your unit before any repair.
Count the blinks
No display? When there is a fault, the OPERATION and TIMER lamps blink a set number of times while ECONOMY flashes fast[1]. Enter the two counts.
How the counts become a code
In every GENERAL table, the OPERATION count is the first character and the TIMER count is the second. Ten blinks stand for A, twelve for C, thirteen for J and fifteen for U, so 5 and 15 blinks is code 5U[2][3]. This is how the tables line up. The manuals do not spell it out in one sentence.
Read the stored code on the remote
- Hold TEST RUN for more than 5 seconds. The remote shows two dashes[1].
- Press the up and down buttons to scroll the codes from 00 to UU. The unit beeps once at each step.
- When the remote shows the stored code, the unit beeps several times and every lamp blinks.
- Press START/STOP to finish. Several beeps at 00 means no error.
Some remotes use a different button to start this check, such as °F/°C[4]. Try it on the remote demo.
All 51 codes
Where a code means different things on different unit types, each wording is listed with the units it applies to.
| Code | Lamps | Meaning and unit types |
|---|---|---|
| 11 | Operation 1 Timer 1 | Serial communication error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted Serial communication error (Serial reverse transfer error) (Outdoor unit) / Serial communication error (Serial forward transfer error) (Indoor unit)[3][8] Wall split inverter, 2023 tables, Ducted, high static 3-phase Serial communication error - reverse transfer outdoor or forward transfer indoor[9] Large wall split inverter |
| 12 | Operation 1 Timer 2 | Wired remote controller communication error[2][3][8] Wall split inverter, earlier tables, Wall split inverter, 2023 tables, Ducted, high static 3-phase Wired remote controller communication error if optional 2-wire remote kit fitted[9] Large wall split inverter |
| 15 | Operation 1 Timer 5 | Check run unfinished[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 18 | Operation 1 Timer 8 | |
| 21 | Operation 2 Timer 1 | |
| 22 | Operation 2 Timer 2 | |
| 23 | Operation 2 Timer 3 | |
| 24 | Operation 2 Timer 4 | |
| 26 | Operation 2 Timer 6 | |
| 27 | Operation 2 Timer 7 | |
| 29 | Operation 2 Timer 9 | |
| 32 | Operation 3 Timer 2 | Indoor unit PCB model information error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 33 | Operation 3 Timer 3 | |
| 35 | Operation 3 Timer 5 | Manual auto switch error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 39 | Operation 3 Timer 9 | |
| 3A | Operation 3 Timer 10 | |
| 41 | Operation 4 Timer 1 | Room temperature sensor error[2][3][9][7][8] Wall split inverter, earlier tables, Wall split inverter, 2023 tables, Large wall split inverter, Ducted, Ducted, high static 3-phase |
| 42 | Operation 4 Timer 2 | Indoor unit Heat Ex. Middle temp. sensor error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted Indoor unit heat exchanger sensor error (Indoor unit)[3][8] Wall split inverter, 2023 tables, Ducted, high static 3-phase |
| 44 | Operation 4 Timer 4 | |
| 51 | Operation 5 Timer 1 | |
| 53 | Operation 5 Timer 3 | |
| 57 | Operation 5 Timer 7 | |
| 58 | Operation 5 Timer 8 | |
| 5U | Operation 5 Timer 15 | |
| 61 | Operation 6 Timer 1 | Outdoor unit missing phase wire error (Outdoor unit) [listed as 'E: 61.5'; wired display 61][8] Ducted, high static 3-phase |
| 62 | Operation 6 Timer 2 | Outdoor unit main PCB model information error or communication error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted Outdoor unit main PCB error (Outdoor unit) / Outdoor Unit Model Information Error (Outdoor unit)[8] Ducted, high static 3-phase |
| 63 | Operation 6 Timer 3 | |
| 64 | Operation 6 Timer 4 | Active filter error, PFC circuit error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 65 | Operation 6 Timer 5 | Trip terminal L error[2][5][6][7][8] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted, Ducted, high static 3-phase |
| 6A | Operation 6 Timer 10 | |
| 71 | Operation 7 Timer 1 | Discharge temp. sensor error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 72 | Operation 7 Timer 2 | Compressor temp. sensor error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 73 | Operation 7 Timer 3 | Outdoor unit Heat Ex. liquid temp. sensor error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted Outdoor unit heat exchanger liquid outlet thermistor error (Outdoor unit) / Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor unit)[8] Ducted, high static 3-phase |
| 74 | Operation 7 Timer 4 | Outdoor temp. sensor error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 75 | Operation 7 Timer 5 | |
| 76 | Operation 7 Timer 6 | |
| 77 | Operation 7 Timer 7 | Heat sink temp. sensor error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 82 | Operation 8 Timer 2 | |
| 83 | Operation 8 Timer 3 | |
| 84 | Operation 8 Timer 4 | |
| 86 | Operation 8 Timer 6 | Discharge pressure sensor error; Suction pressure sensor error; High pressure switch error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted High pressure switch error (Outdoor unit) / Pressure sensor error (Outdoor unit)[8] Ducted, high static 3-phase |
| 94 | Operation 9 Timer 4 | Trip detection[2][5][6][7][8] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted, Ducted, high static 3-phase |
| 95 | Operation 9 Timer 5 | Compressor rotor position detection error[2][5][6][7] Wall split inverter, earlier tables, Cassette, Floor or ceiling, Ducted |
| 97 | Operation 9 Timer 7 | |
| 99 | Operation 9 Timer 9 | |
| A1 | Operation 10 Timer 1 | |
| A3 | Operation 10 Timer 3 | |
| A4 | Operation 10 Timer 4 | |
| A5 | Operation 10 Timer 5 | |
| AC | Operation 10 Timer 12 | |
| J2 | Operation 13 Timer 2 |
Lamps that are not a fault
- OPERATION and TIMER flashing together: the unit is in a cooling test run[2].
- OPERATION blinking slowly while heating: automatic defrost, which can stop the unit for 7 to 15 minutes[10].
- The unit waits about 3 minutes before restarting after it stops or the power returns[11].
The last error stays in memory
The indoor unit stores the last error even after the power is switched off. A new error replaces it. It clears itself after 2 hours of normal running[3].
Codes not in GENERAL's tables
People search for these, but none of them appear in the GENERAL manuals we checked: 13 16 17 1A 28 31 3B 93 9A 9C E1 EC. Some come from other brands. Check the display again or count the blinks.
Stop the unit when
GENERAL's manual says to stop the unit at once, switch off the breaker and call a technician if you smell burning or the lamps flash fast[12].
Sources
- GENERAL Inc. India (general-hvac.com/in, formerly O General / Fujitsu General India): GENERAL (O General) India - RAC Catalogue 2026
- Fujitsu General (hosted on General Airstage Australia support portal, article 6000238748): Fujitsu General INSTALLATION MANUAL, Wall Mounted Type, ASTG09KMCA (indoor), PART No. 9333005126
- Fujitsu General Limited (hosted on General Airstage Australia support portal, article 6000282865): Fujitsu General SERVICE MANUAL, Wall mounted type, ASTH18/22/24KMTD + AOTH18/22/24KMTD (SR_AS109EF_02)
- Fujitsu General (generalww.com, redirected from fujitsu-general.com/shared/ca/): Fujitsu General OPERATION MANUAL, Air Conditioner (Wall-Mounted type) ASUH18/24LPAS, PART No. 9387602265-02
- Fujitsu General (hosted on General Airstage Australia support portal, article 6000238601): Fujitsu General SERVICE MANUAL (short form), Split type, CASSETTE TYPE AUTG18LVLA / AOTG18LACC
- Fujitsu General (hosted on General Airstage Australia support portal, article 6000238602): Fujitsu General SERVICE MANUAL (short form), ABTG18LVTA / AOTG18LACC (cover text reads 'WALL MOUNTED TYPE'; ABT* = under-ceiling/floor-ceiling family per S13)
- Fujitsu General (hosted on General Airstage Australia support portal, article 6000238598): Fujitsu General SERVICE MANUAL (short form), DUCT TYPE ARTG18LLTA / AOTG18LACC
- Fujitsu General (hosted on General Airstage Australia support portal, article 6000286646): Fujitsu General SERVICE MANUAL, Duct type High Static Three Phase, ARTH36/45/54/60KHTA + AOTH36/45/54/60KRTA (SR_AR055EF_04)
- General Airstage Australia: ASTH30/34KNTA - AOTH30/34KNTA Single Phase Wall Hung R32 Split Systems (technical support article)
- GENERAL HVAC Solutions Middle East FZE: GENERAL Middle East & Africa FAQ: Split Systems 0084 / 0039 / 0040 / 0087
- GENERAL Inc.: FAQ: split systems, Middle East and Africa
- GENERAL Inc.: Operating manual, compact wall mounted type (9332280029-04)